IEC Listrik
Volage AC Nominal (50/60Hz) | 60V | 120V | 230V | 230V | ||
Tegangan Operasi Kontinyu Maksimum (AC) | (LN) | Uc | 75V | 150V | 275V | 320V |
(N-PE) | Uc | 255V | 255V | 255V | 255V | |
Nomina Discharge Current(8/20μs) | (LN)/(N-PE) | In | 20 kA/25 KA | |||
Maksimum Discharge Ayeuna (8/20μs) | (LN)/(N-PE) | lmax | 50kA/50KA | |||
Impuls Discharge Ayeuna(10/350μs) | (LN)/(N-PE) | limp | 12,5 kA / 25KA | |||
Énergi spésifik | (LN)/(N-PE) | W/Urang Sunda | 39 kJ/Ω/625KJ/Ω | |||
muatan | (LN)/(N-PE) | Q | 6As / 12.5As | |||
Tingkat panyalindungan tegangan | (LN)/(N-PE) | Up | 700V/1500V 1000V/1500V 1500V/1500V 1600V/1500V/ | |||
Tuturkeun Peunteun Interruptt Ayeuna | (N-PE) | I | 100ARMS | |||
Waktu Tanggapan | (LN)/(N-PE) | tA | <25 ns/<100ns | |||
Sekering Nyadangkeun (maks) | 315A / 250A gG | |||||
Peunteun Arus Sirkuit (AC) | (LN) | lscCR | 25 kA/50 kA | |||
TOV Tahan 5s | (LN) | UT | 114V | 180V | 335V | 335V |
TOV 120 mnt | (LN) | UT | 114V | 230V | 440V | 440V |
Modus | Tahan | Aman Gagal | Aman Gagal | Aman Gagal | ||
TOV Tahan 200s | (N-PE) | UT | 1200V | |||
Jumlah Palabuhan | 1 |
UL Listrik
Tegangan Operasi Kontinyu Maksimum (AC | (LN)/(N-PE) | MCOV | 75V / 255V | 150V / 255V | 275V / 255V | 320V / 255V |
Peunteun Protection tegangan | (LN)/(N-PE) | VPR | 330V / 1200V | 600V / 1200V | 900V / 1200V | 1200V / 1200V |
Nominal Discharge Ayeuna (8/20μs) | (LN)/(-PE) | In | 20KA/20KA | 20KA/20KA | 20KA/20KA | 20KA/20KA |
Peunteun Arus Sirkuit (AC) | (LN) | SCCR | 200KA | 150KA | 150KA | 150KA |
Mékanis & Lingkungan
Kisaran Suhu Operasi | Ta | -40 F nepi ka + 158F [-40℃ka +70℃I |
Kalembaban Operasi Diidinan | RH | 5%…95% |
Tekanan atmosfir sareng luhurna | 80k Pa ... 106k Pa / -500m ... 2000m | |
Torsi screw Terminal | Mmax | 39,9 Ibf-in [4,5 Nm] |
Bagian Palang Konduktor (max) | 2AWG (Padet, Stranded)/4AWG (Fléksibel) | |
35 mm²(Padet, Stranded) / 25 mm²(Fléksibel) | ||
Pamasangan | 35 mm DIN Rel.EN 60715 | |
Gelar panyalindungan | IP 20 (built-in) | |
Bahan Perumahan | Thermoplastic: Extinguishing Gelar UL94V-0 | |
Perlindungan termal | Sumuhun | |
Kaayaan Operasi / Indikasi Sesar | Héjo ok / cacad Beureum | |
Kontak Jauh (RC) | Pilihan | |
RC Ngalihkeun Kamampuh | AC: 250V / 0,5 ABC: 250V / 0,1 A: 125V / 0,2 A; 75V / 0,5A | |
Bagian Palang Konduktor RC (max) | 16AWG (Padet) / 1,5mm²(Dijual) |
Émbaran pesenan
pesenan Kodeu | 75 | 150 | 275 | 320 |
BY1-12.5-XXX/1+1 | 1207513 | 1215013 | 1227513 | 1232013 |
BY1-12.5-XXX/1S+1(jeungkontak jauh) | 1207514 | 1215014 | 1227514 | 1232014 |
BY1-12.5-XXX/0(modul cadang) | 1207501 | 1215001 | 1227501 | 1232001 |
BY1-12.5-NPE/0(modul cadang) | 1205501 | 1255001 | 1225501 | 1225501 |
Katerangan
Jalur L
N Netral
Bumi Pelindung PE
S Signaling Kontak Pilihan
BY1-12.5-XXX/1(S)+1 | 150 | 275 | 320 | 385 |
Unit Tunggal DIN 43880 Dimensi | 1 CTN | |||
Ukuran bungkusan (H × W × L) | [200×230×330mm] | |||
Kuantitas Pesanan Minimum | 32Hijian |
BY1-12.5-XXX/0 | 150 | 275 | 320 | 385 |
BY1-12.5-NPE / 0 | 25 | |||
Unit Tunggal DIN 43880 Dimensi | 1 CTN | |||
Ukuran bungkusan (H × W × L) | [200×230×330mm] | |||
Kuantitas Pesanan Minimum | 64Hijian |